How to Determine the Moisture Content of Concrete Prior to Applying a Sealant or Coating Material


As you may have noticed throughout our blog, we continuously discuss the most important aspects of the job and especially working with any product, is quality control. This is achieved through the execution of application testing. There are various tests that can be conducted across all three of our product offerings (sealants, deck coatings, air barriers). In previous posts, we highlighted various test methods such as ASTM D4541 Pull-Off Adhesion Strength or measuring the wet mil thickness of a coating. For this week’s blog post, we focus on three common methods (ASTM D4263, ASTM F2170, and ASTM F1869) for determining the moisture content prior to applying a sealant or coating material.

The allowable moisture content of concrete prior to the application of sealant or coating materials 5% or less via the internal humidity test (ASTM F2170) or 5lbs/1000ft2 /24hrs via the calcium chloride test (ASTM F1869) when applying to on-grade slabs or unvented elevated slabs. Now, let’s dive into the three common test methods mentioned above.

Rubber Mat Test (Qualitative)

The following (mat) test is to indicate the presence of capillary moisture in concrete per ASTM D4263. This is considered a qualitative test method.

  • Purpose: Capillary moisture in concrete is detrimental to the adhesion and performance of polyurethane deck coatings which cannot tolerate moisture on or within the surface boundary.
  • Materials: 4 mil (minimum) polyethylene sheet or rubber mat 2” duct tape.
  • Conditions: Test when surface and ambient temperatures are within the recommended application temperature for the coating system.
  • Procedure: Tape polyethylene sheet or rubber mat approximately 12”x 12” to the deck surface making certain all edges are sealed. Allow the polyethylene sheet or rubber mat to remain in place for 16 hours (minimum). After 16 hours, remove the polyethylene sheet or rubber mat and observe the underside of the mat and the concrete surface. Slight amounts of moisture are normal and are to be expected. Actual beads of water indicate the concrete is too wet for moisture sensitive coatings to be applied.

 

Internal Humidity Testing of Concrete (Quantitative)

  • Humidity measured inside a drilled hole.
  • Test Method: ASTM F2170
  • Requirement: Maximum 75-80% internal RH considered acceptable for floor coatings
  • Comparable to ~ 5% moisture level

 

If the concrete is at 5.0% moisture content, it will neither absorb nor desorb moisture if the air above it is 70º F (21º C) and 75 percent RH. Therefore, if the air inside the box measures less than 75 percent, it can be assumed that the moisture content of the concrete is less than 5 percent.

Sensor availability:

Wagner Electronic Products, Inc.

326 Pine Grove Rd.

Rogue River OR 97537 USA

http://www.wagnermeters.com/product-category/rapid-rh-and-concrete-moisture-products/  

 

Measuring Moisture Vapor Emission using Calcium Chloride (Quantitative)

  • Moisture vapor emission rate measured and determined over 24hrs via calcium chloride
  • Test Method: ASTM F1869
  • Unit of measure: Pounds per 1000ft2 over a 24hr period (lbs/1000ft2 /24hr)
  • Requirement: Maximum 5lbs/1000ft2 /24hrs allowed prior to floor coating application

 

Test Method Summary: On-site temperature and humidity must be controlled at least 48 hours prior to testing at a setting between 65-85°F and 40-60% relative humidity (RH). The slab must be clean and free of any contaminants. The test method noted below may slightly vary. Refer to the test kit instructions for specific guidelines.

  1. Prepare three test sites for the first 1,000 sq. ft. Add one test site for each additional 1,000 sq.
  2. Set the tape sealed plastic dish on the scale and record its weight in grams, date and time of the test.
  3. Carefully remove the tape along the edge of the dish, invert the lid under the dish and then stick the tape along the side of the dish to keep it safe. Be very careful not to spill any of the calcium chloride.
  4. Place the dish on the slab away from cracks and joints. Be sure the calcium chloride inside is level. Remove the white paper on the dome and place the dome over the dish.
  5. Firmly press the gasket under the flanges of the dome to seat the outer flanges of the dome to the slab and the gasket inside the edge of the dome. Place your hand over the dome and apply pressure, making sure there are no leaks in the gasket.
  6. Place a safety cone over the dome and allow the test kit to remain undisturbed for 60-72 hr.
  7. Cut open the dome and carefully remove the dish. Replace the lid and re-seal it with the blue tape.
  8. Weigh the dish on the same scale, recording the ending weight in grams, the date and time on the dish lid.
  9. Calculate the Moisture Vapor Emission Rate in pounds per 1000ft2 over a 24hr period per the instructions included with the test kit.

 

Be aware that concrete moisture mitigation will be required if the afore-mentioned requirements are not met. Consult Pecora Technical Service with any questions or concerns regarding the published requirements and possible resolutions.

 

Leave a Reply

Your email address will not be published. Required fields are marked *

Back To Blog

Distributor/Sales Rep Locator

Distributor
Sales Rep


Technical Services

Let our tech service experts help make your project a success.

Click or call (800) 523-6688.

Pecora Calculator

Calculate material needs for Coatings, Sealants and Air Barriers.

Launch Calculator




Pecora Calculator
Coatings
Sealants
Air Barrier
Enter Data:
Select Product


Required Dry Mil Coverage (mils)


Total Sq. Ft. Of Project


Estimated Waste (%):
Coverage Rate(Wet):
Sq. Ft./Gallon

Mills


Materials Required
Gallons




To use: Enter values and press "Update" to recalculate. These calculators also update when you tab to the next field or click elsewhere in the page.